Tripping characteristic: C
Number of poles (total): 2
Number of protected poles: 2
Rated current: 32A
Rated voltage: 415V
Rated insulation voltage Ui: 500V
Rated impulse withstand voltage (Uimp): 6kV
Rated short-circuit capacity Icn EN 60898 at 400 V: 3kA
Rated short-circuit capacity Icu IEC 60947-2 at 400 V: 3kA
Voltage type: AC
Frequency: 50Hz - 60Hz
Energy limitation class: 3
Suitable for flush mounting (plasterwork): No
Switched neutral: No
Overvoltage category: 3
Pollution degree: 2
Auxiliary device possible: Yes
Width in module units: 1
Installation depth: 44mm
Degree of protection (IP): IP20
Ambient operating temperature: -25°C - 55°C
Connectable conductor cross-section, stranded: 0.75mm² - 25mm²
Connectable conductor cross-section, solid: 1mm² - 35mm²